Can I sand blast a foundation to prepare the surface for gout?

August 02, 2016/ Ken Gerdes

It is unacceptable to sand blast a foundation in preparation for grout.  Preparation will need to be done with chipping hammers.  A chipping hammer will properly profile the foundation and remove the laitance layer.

Back to FAQs
August 02, 2016/ Ken Gerdes/
Foundation, FAQs
foundation, sand, blast, surface, grout, chipping, hammer, layer, laitance

Ken Gerdes

August 02, 2016

Can I use a high early concrete mixture for my foundation?

August 02, 2016/ Ken Gerdes

A high early concrete should only be used with the approval of the equipment user.  Consider the use of Gill 33 for quick compressive strength and hydration.

Back to FAQs
August 02, 2016/ Ken Gerdes/
FAQs, Foundation
foundation, high, concrete, mix, mixture, Gill 33, strength

Ken Gerdes

August 02, 2016

Can I set multiple pieces of equipment on the same foundation?

August 02, 2016/ Ken Gerdes

Equipment should be set on separate foundation as not to pollute adjacent equipment with sympathetic vibration.

Back to FAQs
August 02, 2016/ Ken Gerdes/
FAQs, Foundation
foundation, can, equipment

Ken Gerdes

August 02, 2016

How big should the foot print of a foundation be?

August 02, 2016/ Ken Gerdes

It should be big enough as to not violate the 30-degree rule.

Back to FAQs
August 02, 2016/ Ken Gerdes/
FAQs, Foundation
foundation, foot print, how, big

Ken Gerdes

August 02, 2016

What is the 30-degree rule?

August 02, 2016/ Ken Gerdes

The 30-degree rule is a best practice.  If you drop a plumb line down from the center of the rotation shaft and rotate this line 30-degrees in both directions, the line should go through the bottom of the foundation and not the side.  This will ensure stability of the foundation.

Back to FAQs
August 02, 2016/ Ken Gerdes/
FAQs, Foundation
foundation, 30, degree, rule, what

Ken Gerdes

August 02, 2016

If there is contamination on an existing foundation can I grout over it?

August 02, 2016/ Ken Gerdes

All existing foundation contamination must be removed by removing the concrete that is contaminated prior to grouting.

Back to FAQs
August 02, 2016/ Ken Gerdes/
Foundation, FAQs
foundation, contamination, remove, removing, concrete

Ken Gerdes

August 02, 2016

What is the maximum allowable height of a foundation?

August 02, 2016/ Ken Gerdes

The maximum height of a foundation should allow a minimum of one and a half inches for grout placement.

Back to FAQs
August 02, 2016/ Ken Gerdes/
Foundation, FAQs
foundation, height, inch, grout

Ken Gerdes

August 02, 2016

How deep should an equipment foundation be placed?

August 02, 2016/ Ken Gerdes

The foundation should be of sufficient depth to prevent damage to the piping or machinery due to frost penetration.  This depth can vary with geography.  Also, consider the 30 degree rule and the required mass.

Back to FAQs
August 02, 2016/ Ken Gerdes/
FAQs, Foundation
foundation, equipment, 30, degree, rule